Failure phenomenon:
There is a magnetic flap level gauge, the normal should be water where it should be red, the water should be white, the current situation is no matter how the water level changes, at the water and gas interface is red, other water and water Some are white, how can I adjust this?
Failure analysis:
1. Verify the process to verify the true value of the liquid level and confirm that there is a liquid level. Or open the diversion to check if there is indeed a liquid level.
2. Check if the upper stop valve is open. If it is confirmed that there is a liquid level check float, switch the shut-off valve and re-enter the magnetic flap level gauge.
Where is the liquid level and where is the float? Since it is red at the water and gas interface, it means that the float is not stuck. This is easy to handle. Simply turn the lower flap at the water and gas interface and turn it into red with a magnet. If you re-use the level gauge, you must lower the liquid level to zero.
Use the magnetic bar to sense on the wall of the tube, confirm the position of the float, confirm that the float is not stuck, and then brush the float part to red, the above is white, if the landlord is not at ease, it can be discharged first, and then re-applied after discharge.
Usually the rotor is stuck, see if the display is damaged, and there is no foreign matter. If not, the float card.